E-MICRO: Minimum Airflow Requirement for E-MICRO Integrated Sensors
Author: Administrator, Created on: Jul 19, 2017 9:38 AM

E-MICRO: Minimum Airflow Requirement for E-MICRO Integrated Sensors

Insufficient airflow can cause the E-MICRO-T(RHP) unit to heat up, which causes the integrated temperature or temperature/humidity sensor to display readings that are not accurate to the rooms’ temperature and relative humidity.

To keep the E-MICRO-T(RHP) unit’s accuracy within ±0.72°F (±0.4°C), place the E-MICRO-T(RHP) unit in an area with more airflow. The minimum airflow needed to prevent the E-MICRO-T(RHP) unit from exceeding this tolerance is 8.2 Ft/S (2.5 M/S).