E-SEMS-16: Get false alerts from the internal humidity sensor.
Author: Administrator, Created on: Oct 22, 2008 2:28 PM

Issue: Get false alerts from the internal humidity sensor every 8 hours to 2 weeks. The alarm email is followed by returned to normal email. Cause: In the sensor configuration, the Sample Period and Alert Delay settings are set too short. Solution: For humidity sensor, set the Sample Period to 10 seconds and the Alert Delay to 30 seconds.