Network Technologies Inc, Innovators in KVM SolutionsWelcome Return to NTI homepage
KVM
SWITCHES
CONSOLE
SWITCHES
KVM
SPLITTER
VIDEO
SWITCHES
VIDEO MATRIX
SWITCHES
VIDEO
SPLITTER
EXTENDERS
via CAT5
KVM
DRAWERS
MONITORS &
ACCESSORIES
SERVER
ENVIRONMENT
VIDEO
CONVERTERS
CABLES &
ADAPTERS



Category: Troubleshooting
Sub-Categories: 0, Documents: 15, Last Update: Feb 7, 2018 11:34 AM

    Advanced Search | Tips  

Documents in Category  
Sort by:
Filter by Document Type:
Document Type: General E-SEMS-16: The sensor graphs do not appear in the web interface after installing the sensors.   
[114] Last Modified: Feb 7, 2018 11:30 AM
Issue: The E-SEMS-16 sensor graphs do not appear in the web interface after installing the sensors Solution: In order to view the E-SEMS-16 sensor graphs after installing the sensors, ensure that you have Java Runtime Environment version 1.5
 
Document Type: General E-SEMS-16: Unable to update the Firmware from version 1.1, 1.2, or 1.3 to version 2.2   
[118] Last Modified: Feb 7, 2018 11:31 AM
Issue: Unable to update the Firmware from version 1.1, 1.2, or 1.3 to version 2.2 Solution: Install Firmware version 2.1 prior to installing version 2.2 on the E-SEMS-16 To download Firmware updates, visit:
 
Document Type: General The NTI Discovery Tool application does not detect any NTI devices   
[119] Last Modified: Feb 6, 2009 2:42 PM
Issue: The NTI Discovery Tool application does not detect any NTI devices. Cause: The NTI Discovery Tool does not detect devices located across sub-nets of a network. Example: A PC running the Discovery Tool application connected to a 192.168.
 
Document Type: General E-SEMS-16: How do I configure the E-SEMS-16 Web Interface to support HTTPS / Protocol 443?   
[136] Last Modified: Feb 7, 2018 11:31 AM
How do I configure the E-SEMS-16 Web Interface to support HTTPS / Protocol 443? The E-SEMS-16 is already configured to support HTTPS / Protocol 443. To connect to the E-SEMS-16 using HTTPS / Protocol 443, change the URL of the browser to HTTPS
 
Document Type: General E-SEMS-16: Get false alerts from the internal humidity sensor.   
[151] Last Modified: Feb 7, 2018 11:26 AM
Issue: Get false alerts from the internal humidity sensor every 8 hours to 2 weeks. The alarm email is followed by returned to normal email. Cause: In the sensor configuration, the Sample Period and Alert Delay settings are set too short.
 
Document Type: General E-SEMS-16: Unit locks up when battery voltage drops below 10.7v.   
[157] Last Modified: Feb 7, 2018 11:32 AM
Issue: E-SEMS-16 locks up when battery voltage drops below 10.7v. Cause: When battery voltage drops below 10.7v, the E-SEMS-16 sends out a battery and power supply alert, which causes the unit to lock up when Firmware version 2.2 or older is
 
Document Type: General E-SEMS-16: Unable to view Sensor data after updating firmware from an earlier version.   
[171] Last Modified: Feb 7, 2018 11:32 AM
Issue: Unable to view Sensor data after updating firmware from an earlier version. A java error is produced similar to the following error: java.lang.NullPointerException at meter26.init(meter26.java:180) at
 
Document Type: General E-SEMS-16: Unable to view Sensor data after updating firmware from an earlier version.   
[172] Last Modified: Feb 7, 2018 11:32 AM
Issue: Unable to view Sensor data after updating firmware from an earlier version. A java error is produced similar to the following: java.lang.NullPointerException at meter26.init(meter26.java:180) at
 
Document Type: General E-GSM(-P), EN-GSMA: The GSM modem is not sending SMS text messages.   
[174] Last Modified: Feb 7, 2018 11:33 AM
Issue: The GSM modem (E-GSM(-P) or E-GSMA) is not sending SMS text messages. Solution: Check that the default baud rate for the Aux port is set to 115200. Check the GSM Modem status message on the Enterprise Settings Screen (in the E-SEMS-16
 
Document Type: General Troubleshooting MRTG Configuration Problems   
[188] Last Modified: Jul 23, 2010 10:03 AM
Issue: The mrtg config file Generated for ENVIROMUX using the on-line available config generator script gives an error "Unknown SNMP var". Solution: Make sure mib file path and mib file name specified at line "LoadMibs:" in config
 
Document Type: General E-SEMS-16: How do I recover the root password?   
[194] Last Modified: Feb 7, 2018 11:33 AM
How do I access/recover the root password of an E-SEMS-x? Steps to Access the Root Password of an E-SEMS-x Unit: 1. Connect a serial cable between a PC and the console port of the E-SEMS-x Unit. Have a Hyperterminal (or other serial com
 
Document Type: General E-SEMS-16: All front panel LEDs are on, unit is unresponsive   
[195] Last Modified: Feb 7, 2018 11:33 AM
Normal 0 false false false MicrosoftInternetExplorer4 /* Style Definitions */ table.MsoNormalTable {mso-style-name:"Table Normal";
 
Document Type: FAQ E-SEMS-16: What do the numerical email error codes mean?   
[130] Last Modified: Feb 7, 2018 11:34 AM
What do the numerical email error codes mean? Given below are the explanations for the numerical email error codes: -1 : Missing Email Address: The destination address field is empty. -4 : No Server. The SMTP Server is unavailable.Try using
 
Document Type: General E-SEMS-16: Unable to update firmware, progress bar hangs.   
[1966] Last Modified: Feb 7, 2018 11:34 AM
E-SEMS-16: Unable to update firmware, progress bar hangs. Issue: Unable to update firmware, progress bar hangs. Cause: User is not logged in as root. Solution: Log into unit as root user. Default password is "admin". If root's
 
Document Type: General E-SEMS-16: Unable to Send Out E-mail Alerts with IMAP or POP ports   
[1609] Last Modified: Feb 7, 2018 11:34 AM
E-SEMS-16: Unable to Send Out E-mail Alerts with IMAP or POP ports Issue: Unable to Send Out E-mail Alerts with IMAP or POP ports. Cause: ENVIROMUX-SEMS-16 does not use IMAP or POP ports. Solution: IMAP and POP ports are only for
 

  Point your RSS reader here for a feed of the latest documents in this category