Use the form below to enter your search criteria. By default, all content is searched except for document comments. If you wish to search comments as well as everything else, click "Also Search Comments" below.
[125]
Comments: 0,
Last Modified: Feb 7, 2018 11:30 AM
- Find Similar
How far can the combination Temperature/Humidity sensor on the E-SEMS-16 be extended? The combination Temperature/Humidity sensor can be extended up to 1000 feet via CAT5/5e/6 cable on the E-SEMS-16. The cables are sold separately.
[2035]
Comments: 0,
Last Modified: Feb 7, 2018 10:32 AM
- Find Similar
-MICRO-TRHP: Receive false alerts from the integrated humidity sensor Issue: Receive false alerts from the integrated humidity sensor every 8 hours to 2 weeks. The alarm ... and the Alert Delay to 30 seconds for the humidity sensor. /* Style
[2089]
Comments: 0,
Last Modified: Feb 7, 2018 10:34 AM
- Find Similar
E-TRHM-E7: How far can the combination Temperature/Humidity sensor be extended? The combination Temperature/Humidity sensor is 7 feet (2 m) in length and includes an RJ45 coupler to extend the sensor up to 500 feet (152 m) using CATx cable (minimum 24AWG) from the E-MICRO. The cables are sold separately.
[32]
Comments: 0,
Last Modified: Feb 7, 2018 10:56 AM
- Find Similar
What types of sensors can the E-MINI use? The E-MINI can use combinations of temperature, humidity, door contact, panic button, and tamper switch sensors. It will also operate with any other Dry Contact sensor within specifications.
[1865]
Comments: 0,
Last Modified: Mar 20, 2013 10:48 AM
- Find Similar
UNIMUX-DVI-xHD: Can the Unit be Shipped in an Environment With Less Than 17% RH With No Adverse Effects? Yes, but only if the unit remains in the packaging box and is put in acceptable temperature and relative humidity environment for at least one hour before opening. Environmental Specifications ... °F (-30 to 60°C). Operating and Storage Relative Humidity: 17 to 90% non-condensing
[2045]
Comments: 0,
Last Modified: Feb 7, 2018 10:36 AM
- Find Similar
causes the integrated temperature or temperature/humidity sensor to display readings that are not accurate to the rooms’ temperature and relative humidity. To keep the E-MICRO-T(RHP) unit
[31]
Comments: 0,
Last Modified: Feb 7, 2018 10:56 AM
- Find Similar
How many sensors can the E-MINI use? The E-MINI can support up to 7 sensors at a time; 2 cat5 sensors, 4 dry contact sensors, and 1 water sensor. The temperature/humidity combination sensors act as 2 sensors in one, in effect allowing up to 9 sensors if combination sensors are used in the cat5 ports.
[2026]
Comments: 0,
Last Modified: Feb 7, 2018 10:37 AM
- Find Similar
/humidity sensors in an E-MICRO may display different readings than the external ... and lower humidity readings, due to the conduction of the printed circuit board material. An increase ... humidity to decrease. To see if the integrated sensor is calibrated correctly, compare the dew point ... sensor. Unlike humidity, dew point is not affected by a temperature increase. If the calculated
[2024]
Comments: 0,
Last Modified: Jan 31, 2018 10:51 AM
- Find Similar
are calibrated correctly The internal temperature/humidity sensors in an E-16D may display different ... higher temperature readings and lower humidity readings, as they are inside a metal case with little ... relative humidity to decrease. To see if the internal sensor is calibrated correctly, compare ... by the external sensor. Unlike humidity, dew point is not affected by a temperature increase. If the calculated
[2025]
Comments: 0,
Last Modified: Feb 7, 2018 11:13 AM
- Find Similar
are calibrated correctly The internal temperature/humidity sensors in an E-5D may display different ... temperature readings and lower humidity readings, as they are inside a metal case with little airflow ... relative humidity to decrease. To see if the internal sensor is calibrated correctly, compare ... sensor. Unlike humidity, dew point is not affected by a temperature increase. If the calculated