E-LD-LCx-y: The Low-Cost Liquid Detection Rope touches metal. Is this a problem or potential problem?
[1852]
Last Modified:
Feb 7, 2018 9:48 AM
E-LD-LCx-y: The Low-Cost Liquid Detection Rope touches metal. Is this a problem or potential problem? The E-LD-LCx-y cannot be in contact with conductive surfaces as it does not have a non-conductive polymer mesh covering the liquid detection
|
|
|
E-LD-LCx-y: The Low-Cost Liquid Detection Rope is routed in such a way that it has to cross over itself. Can this cause problems?
[1851]
Last Modified:
Feb 7, 2018 9:49 AM
E-LD-LCx-y: The Low-Cost Liquid Detection Rope is routed in such a way that it has to cross over itself. Can this cause problems? The E-LD-LCx-y can short and should not be crossed over itself, unlike the E-LD(S)x-y, which has a non-conductive
|
|
|
What is the difference between the E-LD-LCx-y, E-LDx-y and E-LDSx-y?
[1717]
Last Modified:
Feb 7, 2018 9:50 AM
What is the difference between the E-LD-LCx-y, E-LDx-y and E-LDSx-y? The E-LDx-y and E-LDSx-y are essentially the same unit with the same water detection capabilities. They both detect a liquid depth of >0.1” (2.5 mm) and a minimum
|
|
|
E-LDx-y: How can I clean the Liquid Detection Rope?
[1712]
Last Modified:
Feb 7, 2018 9:50 AM
E-LDx-y: How can I clean the Liquid Detection Rope? For periodic maintenance, you can clean the rope with isopropyl alcohol without completely removing the rope from its installed location. Remove the section that you want to clean
|
|
|
E-LDx-y: How can I secure the Liquid Detection Rope to the floor?
[1711]
Last Modified:
Feb 7, 2018 9:50 AM
E-LDx-y: How can I secure the Liquid Detection Rope to the floor? We recommend using our self-adhesive clips, E-CLP10-LD. They are nylon cable clips with a self-adhesive backing. The clips hold the liquid detection rope securely in place
|
|
|
E-LDx-y: The Liquid Detection Rope is routed in such a way that it has to cross over itself. Can this cause false alarms?
[1710]
Last Modified:
Feb 7, 2018 9:48 AM
E-LDx-y: The Liquid Detection Rope is routed in such a way that it has to cross over itself. Can this cause false alarms? No, it will not cause any false alarms. The Liquid Detection Rope has a non-conductive polymer mesh covering two sensing
|
|
|
E-LDx-y: My Liquid Detection Rope touches metal. Is this a problem or potential problem?
[1709]
Last Modified:
Feb 7, 2018 9:48 AM
E-LDx-y: My Liquid Detection Rope touches metal. Is this a problem or potential problem? In general, it is not a problem. The two liquid detection wires are covered by a non-conductive polymer mesh. This mesh isolates the rope from metal
|
|
|
E-LDx-y: How can I test the Liquid Detection Sensor and how often should I test it?
[1708]
Last Modified:
Feb 7, 2018 9:48 AM
E-LDx-y: How can I test the Liquid Detection Sensor and how often should I test it? We recommend testing your leak detection system at least once a year, although some applications may require more frequent testing. System testing should
|
|